The Danfoss FC51 series of inverters, renowned for their powerful features, high durability, and compact size, have become a trusted choice for various industrial applications such as pumps, fans, conveyors, and cooling towers. They are also widely utilized in the HVAC and OEM sectors. In addition to its standard control methods, the Danfoss FC51 inverter supports the Modbus RTU communication protocol. This tutorial will guide you through the process of controlling the Danfoss FC51 using a Mitsubishi Q-Series PLC equipped with the QJ71C24N communication module.
The Danfoss FC51 inverter comes with a built-in RS485 communication port, which simplifies the connection process with the Mitsubishi QJ71C24N module. Below is a wiring diagram illustrating the correct connections between these devices.
Wiring Diagram for QJ71C24N and Danfoss FC51
Explanation:
To control the Danfoss FC51 inverter via Modbus RTU, specific communication parameters must be configured in addition to the standard motor-related settings such as frequency, current, and voltage.
Key Modbus RTU Parameter Settings:
C34F (hex)
C34F = 47C (hex)
or 1148 (dec)
C34F = 847C (hex)
or 33916 (dec)
C34F = 43C (hex)
or 1084 (dec)
C34F = 4BC (hex)
or 1212 (dec)
C359 (hex)
0 to 16384 (dec)
~ (0 to 100%)
16119 (dec)
16129 (dec)
16139 (dec)
Danfoss FC51 Modbus RTU Parameter Settings
The next step is configuring the Mitsubishi QJ71C24N module to communicate effectively with the Danfoss FC51 via Modbus RTU.
Step-by-Step Configuration:
After configuring the QJ71C24N module, the next step is setting up the Modbus RTU protocols for reading and writing data to the Danfoss FC51 inverter.
Configuration via Serial Communication Module Tool:
+Go to Serial Communication Module Tool
+ Protocol Add/Read/Write
D100
D101
D110
D300
D200
D201
D202
D210
(From D210 onwards, depending on the number of registers read)D300
With the configuration complete, the final step is to create a PLC program that controls the Danfoss FC51 inverter through the QJ71C24N module.
Sample PLC Program Overview:
This detailed guide provides all the necessary steps to configure and control the Danfoss FC51 inverter using the Mitsubishi QJ71C24N module via the Modbus RTU protocol. The tutorial covers wiring diagrams, Modbus configuration, and practical PLC programming examples, ensuring a smooth and efficient setup. For a visual guide, refer to the images provided throughout the tutorial.
Smart Asset Tracking & Monitoring Solution for Process...
Smart Utility Management Solution Smart Utility Management...
Revolutionizing with Mobile Solutions Over the past decade,...
Maximizing Manufacturing Productivity with OEE Understanding...
Real-Time Data Analysis Unlike traditional preventive...
Optimizing Industrial Alarm Management: Enhancing Plant...
Condition-Based Maintenance (CbM) Optimizing Maintenance for...