Authored by Faizal Afzal
The Delta VFD-M series, though discontinued and replaced by newer models like the MS300, remains a prevalent choice in industrial machinery. Due to its widespread use, there are still many instances where engineers and technicians need to interface with this older inverter model. This guide will walk you through the process of using a MicroLogix 1400 PLC to control a Delta VFD-M inverter via Modbus-RTU (RS485) communication.
This tutorial provides detailed instructions on wiring, parameter configuration, and programming to ensure a seamless and efficient setup.
To begin, you need to establish the correct wiring connections between the MicroLogix 1400 PLC and the Delta VFD-M inverter. The preferred method is using the 1763-NC01 module for easy wiring; however, direct connections to the RS485 port of the MicroLogix 1400 PLC (Mini DIN – 8 Pin) are also possible.
MicroLogix 1400 & Delta VFD-M Wiring Diagram
Wiring Tips:
For successful communication and control of the Delta VFD-M via Modbus-RTU, certain parameters need to be configured on the inverter. These configurations align the VFD’s communication settings with those of the MicroLogix 1400 PLC.
Essential Parameter Configurations:
These parameters ensure that the Delta VFD-M is properly set up to receive and respond to commands from the MicroLogix 1400 PLC via Modbus-RTU.
Controlling the Delta VFD-M involves writing specific values to its Modbus registers. Here, we will cover the main register addresses used for motor control and frequency setting.
Motor Control Register Address:
Frequency Setting Register Address:
Delta VFD-M Control Register Table
These register addresses and corresponding values allow you to control the basic operations of the VFD, such as starting, stopping, and adjusting the motor speed.
Monitoring the Delta VFD-M’s performance involves reading specific output registers. These registers provide real-time data on various operational parameters, including frequency, current, and voltage.
Monitoring Register Addresses:
Faizal Afzal recommends reading five output registers to monitor:
Delta VFD-M Monitoring Register Table
These monitoring addresses are essential for tracking the VFD’s operational status and ensuring it functions correctly within the desired parameters.
To establish communication between the MicroLogix 1400 PLC and the Delta VFD-M, you need to configure Channel 0 on the PLC for RS485 communication. The settings must match the communication parameters set on the VFD.
Channel 0 (RS485) Configuration Steps:
MicroLogix 1400 RS485 Configuration Screen
Proper configuration ensures that the MicroLogix 1400 PLC can successfully communicate with and control the Delta VFD-M.
Finally, you will need to program the MicroLogix 1400 PLC to handle both the control and monitoring tasks for the Delta VFD-M. Below are the critical programming components required for effective VFD management.
Programming Components:
These programming steps integrate the control and monitoring of the Delta VFD-M into your automation system, providing seamless operation and feedback.
This professional guide provides a comprehensive approach to controlling the Delta VFD-M using a MicroLogix 1400 PLC via Modbus-RTU communication. From wiring and parameter configuration to PLC programming, each step is designed to ensure that you can efficiently and effectively manage the VFD within your industrial processes.
By following this guide, you will be able to maintain and control older Delta VFD-M inverters, ensuring continued reliability and performance in your operations.
Smart Asset Tracking & Monitoring Solution for Process...
Smart Utility Management Solution Smart Utility Management...
Revolutionizing with Mobile Solutions Over the past decade,...
Maximizing Manufacturing Productivity with OEE Understanding...
Real-Time Data Analysis Unlike traditional preventive...
Optimizing Industrial Alarm Management: Enhancing Plant...
Condition-Based Maintenance (CbM) Optimizing Maintenance for...